Technical Documents
Specifications
Product Details
This limit switch is a Compact safety device designed to detect mechanical position changes and provide dependable switching for industrial automation and machinery. It is a miniature safety limit switch suited to a range of actuator options and conduit/connector styles, enabling straightforward integration into control systems where direct‑opening contact behaviour and defined operating characteristics are required.
A connector and Terminal arrangement is provided with screw Terminal and M12 connector variants
wiring should follow the terminal‑numbering standard and use crimp terminals AWG20 to AWG18 (0.5 to 0.75 mm2).
It is specified that a 10A gI or gG fuse compliant with IEC 269 should be used in series as short‑circuit protection
this fuse is not built into the unit.
Rated insulation voltage is 300V and impulse withstand voltages range from 2.5 kV to 6 kV between specified terminals and uncharged metallic parts.
Mounting requires M4 screws with specified torques and correct dog alignment at right angles to the actuator
improper leverage or slanted loading may damage the actuator.
A direct‑opening mechanism physically forces separation of NC contacts, ensuring positive opening even when contact deposits occur.
Stock information temporarily unavailable.
€ 32.71
€ 32.71 Each (ex VAT)
1
€ 32.71
€ 32.71 Each (ex VAT)
Stock information temporarily unavailable.
1
Technical Documents
Specifications
Product Details
This limit switch is a Compact safety device designed to detect mechanical position changes and provide dependable switching for industrial automation and machinery. It is a miniature safety limit switch suited to a range of actuator options and conduit/connector styles, enabling straightforward integration into control systems where direct‑opening contact behaviour and defined operating characteristics are required.
A connector and Terminal arrangement is provided with screw Terminal and M12 connector variants
wiring should follow the terminal‑numbering standard and use crimp terminals AWG20 to AWG18 (0.5 to 0.75 mm2).
It is specified that a 10A gI or gG fuse compliant with IEC 269 should be used in series as short‑circuit protection
this fuse is not built into the unit.
Rated insulation voltage is 300V and impulse withstand voltages range from 2.5 kV to 6 kV between specified terminals and uncharged metallic parts.
Mounting requires M4 screws with specified torques and correct dog alignment at right angles to the actuator
improper leverage or slanted loading may damage the actuator.
A direct‑opening mechanism physically forces separation of NC contacts, ensuring positive opening even when contact deposits occur.